Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21
Overview:
Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21
Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21
are used to prevent process medium form entering directly into the pressure-sensing assembly of the differential pressure transmitter, they are connected to the transmitter using capillaries filled with fill fluid.
Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21
EJX118A Diaphragm Sealed Differential Pressure Transmitters can be used to measure liquid, gas, or steam flow, as well as liquid level, density, and
pressure. EJX118A outputs a 4 to 20 mA DC signal corresponding to the measured differential pressure.
Its highly accurate and stable sensor can also measure the static pressure which can be shown on the integral indicator or remotely monitored via BRAIN or HART communications. Other key features include quick response, remote set-up using communications, and diagnostics and optional status output for
pressure high/low alarm. The multi-sensing technology provides the advanced diagnostic function to detect such abnormality as an impulse line blockage.
FOUNDATION Fieldbus and PROFIBUS PA protocol types are also available. All EJX series models in their standard configuration, with the exception of the Fieldbus and PROFIBUS types, are certified by TÜV as complying with SIL 2 for safety requirement.
STANDARD SPECIFICATIONS
Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21
Refer to GS 01C25T02-01EN for Fieldbus communication type and GS 01C25T04-01EN for PROFIBUS PA communication type for the items marked with “◊.”
SPAN AND RANGE LIMITS
Measurement
Span/Range
|
kPa
|
inH2O (/D1)
|
mbar
(/D3)
|
mmH2O (/D4)
|
M
|
Span
|
2 to 100
|
8 to 400
|
20 to 1000
|
200 to
10000
|
Range
|
-100 to
100
|
-400 to
400
|
-1000 to
1000
|
-10000 to
10000
|
H
|
Span
|
10 to 500
|
40 to 2000
|
100 to
5000
|
0.1 to 5 kgf/cm2
|
Range
|
-500 to
500
|
-2000 to
2000
|
-5000 to
5000
|
-5 to 5 kgf/cm2
|
PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted parts material code SW for 3-inch flange flush type, fill fluid code B, and capillary length of 5 m.
For Fieldbus and PROFIBUS PA communication types, use caribrated range instead of span in the following specifications.
Specification Conformance
EJX series ensures specification conformance to at least ±3σ.
MODEL AND SUFFIX CODES
Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21
Model
|
Suffix Codes
|
Description
|
EJX118A
|
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
|
Diaphragm sealed differential pressure transmitter
|
Output signal
|
-D . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-J . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-F . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
-G . . . . . . . . . . . . . . . . . . . . . . . . . . . . .
|
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART 5 protocol)
4 to 20 mA DC with digital communication (HART 5 / HART 7 protocol) (Refer to GS 01C25T01-01EN)
Digital communication (FOUNDATION Fieldbus protocol, refer to
GS 01C25T02-01EN)
Digital communication (PROFIBUS PA protocol, refer to
GS 01C25T04-01EN)
|
Measurement span (capsule)
|
M . . . . . . . . . . . . . . . . . . . . . . . . . . . H . . . . . . . . . . . . . . . . . . . . . . . . . . . .
|
2 to 100 kPa (8 to 400 inH2O)
10 to 500 kPa (40 to 2000 inH2O)
|
─
|
S . . . . . . . . . . . . . . . . . . . . . . . . .
|
Always S
|
─
|
C . . . . . . . . . . . . . . . . . . . . . .
|
Always C
|
Coverflange bolts and nuts material
|
J . . . . . . . . . . . . . . . . . . . . G. . . . . . . . . . . . . . . . . . . . C . . . . . . . . . . . . . . . . . . . .
|
B7 carbon steel
316L SST
660 SST
|
Installation
|
-9 . . . . . . . . . . . . . . . .
|
Horizontal piping type and left side high pressure
|
Amplifier housing
|
1 . . . . . . . . . . . . . . .
3 . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . .
|
Cast aluminum alloy
Cast aluminum alloy with corrosion resistance properties*1
ASTM CF-8M stainless steel*2
|
Electrical connection
►
|
0 . . . . . . . . . . . .
2 . . . . . . . . . . . .
4 . . . . . . . . . . . .
5 . . . . . . . . . . . .
7 . . . . . . . . . . . .
9 . . . . . . . . . . . . A . . . . . . . . . . . . C . . . . . . . . . . . . D . . . . . . . . . . . .
|
G 1/2 female, one electrical connection without blind plugs
1/2 NPT female, two electrical connections without blind plugs
M20 female, two electrical connections without blind plugs
G 1/2 female, two electrical connections with a blind plug *3
1/2 NPT female, two electrical connections with a blind plug *3
M20 female, two electrical connections with a blind plug *3
G1/2 female, two electrical connections and a 316 SST blind plug
1/2 NPT female, two electrical connections and a 316 SST blind plug
M20 female, two electrical connections and a 316 SST blind plug
|
Integral indicator
►
|
D . . . . . . . . . E . . . . . . . . . N . . . . . . . . .
|
Digital indicator *4
Digital indicator with the range setting switch (push button) *5
None
|
Mounting bracket
►
|
B . . . . . . J . . . . . . N . . . . . .
|
304 SST 2-inch pipe mounting, flat type (for horizontal piping)
316 SST 2-inch pipe mounting, flat type (for horizontal piping) None
|
Diaphragm seal section
|
Continued on diaphragm seal section (II)
|
|
|
|
|
|
|
|
|
|
|
|
|
The “►” marks indicate the most typical selection for each specification
*1: Not applicable for electrical connection code 0, 5, 7, 9 and A. Content rate of copper in the material is 0.03% or less and content rate of iron is 0.15% or less.
*2: Not applicable for electrical connection code 0, 5, 7 and 9.
*3: Material of a blind plug is aluminum alloy or 304 SST
*4: Not applicable for output signal code G.
*5: Not applicable for output signal code F.
Yokogawa Pressure Transmitter EJX118A-WJ13A1SW0-AA21