STANDARD SPECIFICATIONS

Yokogawa Analog Output Modules for ProSafe-RS SDV526-S33

 Output Module

Yokogawa Analog Output Modules for ProSafe-RS SDV526-S33

Item

Specifications

Model

SDV526 (*1)

Number of outputs

4-channel, module isolation

Output voltage

100 to 120 V AC

 

Output voltage drop

1.3 V AC + 0.01 V AC/m minimum

2.5 V AC + 0.04 V AC/m maximum (*2)

External power supply rating

100 to 120 V AC (*5)

External power supply

100 to 120 V AC +10 %/–15 %

Maximum leak current at output off status

 

2 mA

Output format

Current source (common N side)

Maximum load current

0.5 A/output line

Minimum load current

0.1 A/output line

Load resistance range

5 k (*3)

Output response time

60 ms

Withstand voltage

1500 V AC (between output signal lines and system)

 

Current consumption

500 mA maximum (5 V DC)

50 mA maximum (24 V DC)

Weight

0.36 kg

External connection

Dedicated signal cable (AKB652) (*4)

      *1:      SDV526 is not capable to of detecting the following faults.

- short circuit between channels

- output short circuit while output signals are off

Set minimum output holding time to one second. Acceptable reverse electromotive voltage for output channel is 450 V, 1 ms (The reverse electromotive voltage is caused by the connection with inductive load such as relays or solenoid valves.) Supported by R2.02.00 or later.

*2:      It depends on the length of AKB652.

*3:      Resistance value of the load for OFF state, including the field wiring resistance.

*4:      For dual-redundant configuration, two AKB652 cables with the same length should be used.

*5:     In order to comply with the CE Marking Low Voltage Directive, SDV526 has to limit its connection to the external power supply terminal only with the secondary circuit. Reinforced insulation is required by EN 61010-1:2010 using an isolation transformer or alike. This means that 100-120V AC isolated from main power supply has to connect with SDV526.


MODEL AND SUFFIX CODES

Yokogawa Analog Output Modules for ProSafe-RS SDV526-S33

 

 

Description

Model

SDV526

Digital Output Module (4-channel, module isolation)

 

 

Suffix Codes

-S

Standard type (*1)

3

With signal cable interface adapter

3

With ISA Standard G3 and temperature (-20 to 70 °C)

*1:      with prevention of false insertion