Product Information

Yokogawa ProSafe-RS Analog Output Module SDV521-S63[Product print page]

Product Name: Yokogawa ProSafe-RS Analog Output Module SDV521-S63
Product Type: SDV521-S63
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa ProSafe-RS Analog Output Module SDV521-S63 can be mounted on the safety node unit and the safety control unit Yokogawa ProSafe-RS Analog Output Module SDV521-S63 Yokogawa ProSafe-RS Yokogawa SIS (Safety Instrumented Systems)


 Detailed description

Yokogawa ProSafe-RS Analog Output Module SDV521-S63


STANDARD SPECIFICATIONS

 Output Module

Yokogawa ProSafe-RS Analog Output Module SDV521-S63

Item

Specifications

Model

SDV521

Number of outputs

4-channel, module isolation

Output voltage

24 V DC

Output voltage drop

1 V maximum

External power supply rating

24 V DC, 10 A minimum

 

External power supply

24 V DC +20 %/–10 % Current capacity: 8.2 A (*1)

Maximum leak current at output off status

 

1.6 mA

Output format

Current source

Maximum load current

2 A/output line (8 A in total output lines) (*2)

Minimum load current

100 mA

Load resistance range

12 to 240 (*3)

Output response time

30 ms maximum

 

Withstand voltage

2 kV AC (between output signal lines and system), 4-point input lines collectively connected (negative lines)

 

Current consumption

280 mA maximum (5 V DC)

140 mA maximum (24 V DC)

Weight

0.36 kg

External connection

Dedicated signal cable (AKB651)

*1:      Required capacity when all the channels are loaded with rated load. Please use external source with the capacity most appropriate for load to be applied. Yokogawa ProSafe-RS Analog Output Module SDV521-S63 (When it is probable to get inrush load, use power source with the inrush current added.)

*2:      1 A for filament lamp under the specified conditions. When rush current is over 10 A, the module cannot be connected.

*3:      Resistance value of the load for both ON and OFF state, including the field wiring resistance. Yokogawa ProSafe-RS Analog Output Module SDV521-S63


MODEL AND SUFFIX CODES

Yokogawa ProSafe-RS Analog Output Module SDV521-S63

 

 

Description

Model

SDV521

Digital Output Module (4-channel, module isolation)

 

 

Suffix Codes

-S

Standard type

6

With signal cable interface adapter and no explosion protection

F

With signal cable interface adapter and explosion protection

3

With ISA Standard G3 and temperature (-20 to 70 °C)

Option Codes

/PRP

With prevention pin of false insertion