Product Information

Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3[Product print page]

Product Name: Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3
Product Type: SDV144-SE3
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3 can be mounted on the safety node unit and the safety control unit Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3


 Detailed description

Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3

STANDARD SPECIFICATIONS

Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3

 Input Module

 Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3 accept contact signals from the field. SDV144-SE3 can be made dual-redundant.

Item

Specifications

Model

SDV144

Number of inputs

16-channel, module isolation

 

Input signal

No-voltage contact ON: 1 k maximum OFF: 100 k minimum

 

Input current

6 mA ± 20 %

(External power supply, 24 V DC at 0 input)

Contact rating

24 V DC +20 % / -10 % (*1), 10 mA or greater

 

External power supply

24 V DC +20 % / -10 % (*1) Current capacity: 200 mA

Instantaneous maximum permissible input voltage

 

30.0 V DC

Input response time

40 ms maximum

Withstand voltage

2 kV AC between input signal and system, 16-input line collectively connected (*2)

 

Current consumption

290 mA maximum (5 V DC)

140 mA maximum (24 V DC)

 

Weight

0.36 kg (For pressure clamp terminal block or MIL cable)

0.41 kg (With signal cable interface adapter)

 

External connection

Pressure clamp terminal

MIL cable

Dedicated signal cable (AKB331)

*1:      The contact rating and the external power supply of SDV144-SE3 style code S1, S2 and S3 are 24 V DC ± 5 %.

*2:      When connecting SDV144-SE3 and SED4D terminal board using the dedicated signal cable, the withstand voltage is 500 V AC (between input signal lines and system). If MIL connector cables are used, the withstand voltage depends on their cable’s electrical specifications.


MODEL AND SUFFIX CODES

Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3

Digital Input Module


 

 

Description

Model

SDV144

Digital Input Module (16-channel, module isolation)

 

 

 

 

Suffix Codes

-S

Standard type

5

For pressure clamp terminal block or MIL cable with no explosion protection

6

With signal cable interface adapter and no explosion protection (*1)

E

For pressure clamp terminal block or MIL cable with explosion protection

F

With signal cable interface adapter and explosion protection (*1)

3

With ISA Standard G3 and temperature (-20 to 70 °C)

 

 

 

 

 

Option Codes

/B4S00

With pressure clamp terminal block for digital input (without surge absorber) [Model: STB4S-00]

/B4S10

With pressure clamp terminal block for digital input (with surge absorber) [Model: STB4S-10]

 

/B4D00

Dual-redundant pressure clamp terminal block for digital input (without surge absorber) (*2) [Model: STB4D-00]

 

/B4D10

Dual-redundant pressure clamp terminal block for digital input (with surge absorber) (*2) [Model: STB4D-10]

/PRP

With prevention pin of false insertion (*3)

/CCC01

With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]

/CCC02

With connector cover for MIL cable (for discrete wire) [Model: SCCC02]

*1:      When SDV144-SE3-S63 or -SF3 is selected, you cannot choose the option code for a pressure clamp terminal block and MIL

cable connector.

*2:      When this module is used in dual-redundant configuration, order an additional module with the same specification but without option codes.

*3:      When SDV144-SE3-S63 or -SF3 is selected, you can choose the option code for prevention pin of false insertion.

Yokogawa Analog Input Modules for ProSafe-RS SDV144-SE3