Product Information

Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63[Product print page]

Product Name: Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63
Product Type: SAR145-S63
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63 can be mounted on the safety node unit and the safety control unit Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63


 Detailed description

Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63

STANDARD SPECIFICATIONS

Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63

RTD Input Module

Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63 inputs RTD signals from the field. The SAR145 can be made dual redundant.

Item

Specifications

Model

SAR145

Number of input channels

16-channel, Isolated Channels

 

 

Input signal (*5)

 

RTD (3 wires)

JIS C 1604-1997 (*3), IEC60751-1995:  Pt100, Pt50, Pt200, Pt500, Pt1000

DIN 43760-1987: Ni100

Minco: Ni120

 

Withstand voltage

Between input and system: 1500 V AC, For 1 minute

Between channels: 200 V AC, For 1 minute

 

 

Accuracy

(*1) (*2)

800 Ω range

to 400 Ω: ± 160 mΩ

to 800 Ω: ± 180 mΩ

4000 Ω range

to 2000 Ω: ± 900 mΩ

to 4000 Ω: ± 1700 mΩ

Allowable resistance of wiring

150 Ω or less (wiring resistance per wire) (*4)

 

Measurement current

800 Ω range: 0.5 mA

4000 Ω range: 0.1 mA

 

 

Temperature drift

800 Ω range

to 400 Ω: ± 150 mΩ / 10 ºC

to 800 Ω: ± 300 mΩ / 10 ºC

4000 Ω range

to 2000 Ω: ± 750 mΩ / 10 ºC

to 4000 Ω: ± 1500 mΩ / 10 ºC

Data update period

150 ms

 

Burn-out

Individual channel setting

Setting: Burnout upscale/Burnout downscale

Detection time: 1.5 s

Ambient temperature (during operation)

-20 to + 70 ºC

 

Maximum current consumption

5 V system: 500 mA

24 V system: 200 mA

Weight

0.47 kg

External connection

Dedicated signal cable (AKB611)

*1:     Include the tolerance which is caused by dedicated signal cable AKB611(up to 5 m).

In case of the cable length of AKB611 is more than 5 m, 15 mΩ shall be added to the accuracy per each 5 m.

*2:     These values apply for the case when the resistance of field wiring line A and line B are the same value.

If the difference of resistance between line A and line B happens, the different value among them needs to be added.

*3:      SAR145 also supports JIS C 1604-1989 JPt100.

*4:      Wiring resistance for signal cable of INnA, INnB and INnC must be identical.

*5:   When connecting the RTD modules, use the resisters composed of the passive parts. If an instrument that simulates resistance electronically is connected, it may cause error between reading and actual values. Do not connect voltage signal to the modules.

MODEL AND SUFFIX CODES

Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63

 

 

Description

Model

SAR145

RTD Input Module (16-channel, Isolated Channels)

 

 

Suffix Codes

-S

Standard type

6

With signal cable interface adapter and no explosion protection

F

With signal cable interface adapter and explosion protection

3

With ISA Standard G3 and temperature (-20 to 70 ºC)

Option Codes

/PRP

With prevention pin of false insertion


Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63