Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63
STANDARD SPECIFICATIONS
RTD Input Module
Yokogawa Analog I/O Modules (for ProSafe-RS) SAR145-S63 inputs RTD signals from the field. The SAR145 can be made dual redundant.
Item
Specifications
Model
SAR145
Number of input channels
16-channel, Isolated Channels
Input signal (*5)
RTD (3 wires)
JIS C 1604-1997 (*3), IEC60751-1995: Pt100, Pt50, Pt200, Pt500, Pt1000
DIN 43760-1987: Ni100
Minco: Ni120
Withstand voltage
Between input and system: 1500 V AC, For 1 minute
Between channels: 200 V AC, For 1 minute
Accuracy
(*1) (*2)
800 Ω range
to 400 Ω: ± 160 mΩ
to 800 Ω: ± 180 mΩ
4000 Ω range
to 2000 Ω: ± 900 mΩ
to 4000 Ω: ± 1700 mΩ
Allowable resistance of wiring
150 Ω or less (wiring resistance per wire) (*4)
Measurement current
800 Ω range: 0.5 mA
4000 Ω range: 0.1 mA
Temperature drift
to 400 Ω: ± 150 mΩ / 10 ºC
to 800 Ω: ± 300 mΩ / 10 ºC
to 2000 Ω: ± 750 mΩ / 10 ºC
to 4000 Ω: ± 1500 mΩ / 10 ºC
Data update period
150 ms
Burn-out
Individual channel setting
Setting: Burnout upscale/Burnout downscale
Detection time: 1.5 s
Ambient temperature (during operation)
-20 to + 70 ºC
Maximum current consumption
5 V system: 500 mA
24 V system: 200 mA
Weight
0.47 kg
External connection
Dedicated signal cable (AKB611)
*1: Include the tolerance which is caused by dedicated signal cable AKB611(up to 5 m).
In case of the cable length of AKB611 is more than 5 m, 15 mΩ shall be added to the accuracy per each 5 m.
*2: These values apply for the case when the resistance of field wiring line A and line B are the same value.
If the difference of resistance between line A and line B happens, the different value among them needs to be added.
*3: SAR145 also supports JIS C 1604-1989 JPt100.
*4: Wiring resistance for signal cable of INnA, INnB and INnC must be identical.
*5: When connecting the RTD modules, use the resisters composed of the passive parts. If an instrument that simulates resistance electronically is connected, it may cause error between reading and actual values. Do not connect voltage signal to the modules.
Description
RTD Input Module (16-channel, Isolated Channels)
Suffix Codes
-S
Standard type
6
With signal cable interface adapter and no explosion protection
F
With signal cable interface adapter and explosion protection
3
With ISA Standard G3 and temperature (-20 to 70 ºC)
Option Codes
/PRP
With prevention pin of false insertion