Yokogawa Analog I/O Modules (for ProSafe-RS) SAT145-S63
STANDARD SPECIFICATIONS
TC/mV Input Module
Yokogawa Analog I/O Modules (for ProSafe-RS) SAT145-S63 receives signals from mV and thermocouple (TC). The SAT145 can be made dual redundant.
Item
Specifications
Model
SAT145
Number of input channels
16-channel, Isolated Channels
Input signal
TC: JIS C 1602:1995, IEC60584:1995
J: -210 to 1200 °C K: -270 to 1372 °C E: -270 to 1000 °C T: -270 to 400 °C
S: -50 to 1767 °C R: -50 to 1767 °C N: -270 to 1300 °C B: 42 to 1820 °C
mV
-100 to 150 mV, -20 to 80 mV, -5 to 25 mV
Switching input signals
TC/mV can be set individually for CH1 to CH16.
Permissible input range
± 5 V
Withstand voltage (*1)
Between input and system: 1500 V AC for 1 minute
Between channels: 200 V AC for 1 minute
Input impedance
At least 1 MΩ during Power-ON At least 1 MΩ during Power-OFF
Accuracy
TC ± 40 μV
mV ± 40 μV
Allowable total resistance of signal source plus wiring
1000 Ω or less
Effect of allowable signal source resistance (1000 Ω)
± 20 μV (*2)
Reference junction compensation accuracy (*3) (*4)
-20 to 0 °C ± 1.5 °C
0 to 30 °C ± 1.0 °C
30 to 70 °C ± 1.5 °C
Temperature drift
± 40 μV / 10 °C
Data update period
150 ms
Burn-out
Individual channel setting
Setting: Burnout upscale/Burnout downscale
Detection time: 1.5 s
Ambient temperature (during operation)
-20 to 70 °C
Maximum current consumption
5 V system: 400 mA
24 V system: 200 mA
Weight
0.47 kg
External connection
Dedicated signal cable (AKB331)
*1: Use AKB331 of style code S3.
*2: In dual redundant configuration, this effect is ± 40 μV.
*3: Reference junction compensation accuracy is specified on combination with SBT4D.
It varies depending on the temperature environment of SBT4D.
These values indicate Reference junction compensation accuracy against the ambient temperature of terminal board.
*4: This accuracy changes due to the installation condition.
If measured temperature is lower than 0 °C, multiply the above value by the following coefficient (K):
Description Model SAT145 TC/mV Input Module (16-channel, Isolated Channels) Suffix Codes -S Standard type 6 With signal cable interface adapter and no explosion protection F With signal cable interface adapter and explosion protection 3 With ISA Standard G3 and temperature (-20 to 70 ºC) Option Codes /PRP With prevention pin of false insertion
Description
TC/mV Input Module (16-channel, Isolated Channels)
Suffix Codes
-S
Standard type
6
With signal cable interface adapter and no explosion protection
F
With signal cable interface adapter and explosion protection
3
With ISA Standard G3 and temperature (-20 to 70 ºC)
Option Codes
/PRP
With prevention pin of false insertion
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.