Product Information

Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3[Product print page]

Product Name: Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3
Product Type: SAV144-SE3
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3 can be mounted on the safety node unit and the safety control unit Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3


 Detailed description

Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3

STANDARD SPECIFICATIONS

Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3

Voltage Input Module

Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3 inputs 1 to 5 V/1 to 10 V signals from the field. The SAV144 can be made dual redundant.

Item

Specifications

Model

SAV144

Number of input channels

16-channel, module isolation

Rated input range

1 to 5 V/1 to 10 V

Permissible input range

±30 V

Input impedance during P-ON

1 M

Input impedance during P-OFF

100 k

 

Rated accuracy

1 to 5 V: ±4 mV

1 to 10 V: ±9 mV

Data update frequency

40 ms

 

Temperature drift

1 to 5 V: ±4 mV/10 °C

1 to 10 V: ±9 mV/10 °C

Withstand voltage

1.5 kV AC between input signal and system (*1)

 

Maximum current consumption

5 V system: 300 mA

24 V system: 140 mA

 

Weight

0.24 kg (For pressure clamp terminal block or MIL cable)

0.29 kg (With signal cable interface adapter)

 

External connection

Pressure clamp terminal

MIL cable

Dedicated signal cable (KS1)

*1:      500 V AC when dedicated signal cable is used.



MODEL AND SUFFIX CODES

Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-SE3

 

 

Description

Model

SAV144

Analog input module (1 to 5 V/1 to 10 V, 16-channel, module isolation)

 

 

 

 

Suffix Codes

-S

Standard type

5

For pressure clamp terminal block or MIL cable with no explosion protection

6

With signal cable interface adapter and no explosion protection (*1)

E

For pressure clamp terminal block or MIL cable with explosion protection

F

With signal cable interface adapter and explosion protection (*1)

3

With ISA Standard G3 and temperature (-20 to 70 ºC)

 

 

 

 

 

 

Option Codes

 

/A4S00

With pressure clamp terminal block for analog

[Model: STA4S-00]

 

/A4S10

With pressure clamp terminal block for analog (with surge absorber) [Model: STA4S-10]

 

/A4D00

With dual-redundant pressure clamp terminal block for analog (*2) [Model: STA4D-00]

 

/A4D10

With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*2) [Part name: STA4D-10]

/PRP

With prevention pin of false insertion (*3)

 

/CCC01

With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]


*1:      When selecting SAV144-S63 or -SF3, you can not choose the option code of pressure clamp terminal block and MIL cable connector.

*2:      When using this module in a dual-redundant configuration, order an additional module with the same specifications but without option codes.

*3:      When SAV144-S63 or -SF3 is selected, you can choose the option code for prevention pin of false insertion.

A mechanism to prevent wrong type I/O module insertion is supported with signal cable. The signal cable used with this I/O

module must have option code /SAV144.