Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-S53
STANDARD SPECIFICATIONS
Voltage Input Module
Yokogawa Analog I/O Modules (for ProSafe-RS) SAV144-S53 inputs 1 to 5 V/1 to 10 V signals from the field. The SAV144 can be made dual redundant.
Item
Specifications
Model
SAV144
Number of input channels
16-channel, module isolation
Rated input range
1 to 5 V/1 to 10 V
Permissible input range
±30 V
Input impedance during P-ON
1 MΩ
Input impedance during P-OFF
100 kΩ
Rated accuracy
1 to 5 V: ±4 mV
1 to 10 V: ±9 mV
Data update frequency
40 ms
Temperature drift
1 to 5 V: ±4 mV/10 °C
1 to 10 V: ±9 mV/10 °C
Withstand voltage
1.5 kV AC between input signal and system (*1)
Maximum current consumption
5 V system: 300 mA
24 V system: 140 mA
Weight
0.24 kg (For pressure clamp terminal block or MIL cable)
0.29 kg (With signal cable interface adapter)
External connection
Pressure clamp terminal
MIL cable
Dedicated signal cable (KS1)
*1: 500 V AC when dedicated signal cable is used.
Description
Analog input module (1 to 5 V/1 to 10 V, 16-channel, module isolation)
Suffix Codes
-S
Standard type
5
For pressure clamp terminal block or MIL cable with no explosion protection
6
With signal cable interface adapter and no explosion protection (*1)
E
For pressure clamp terminal block or MIL cable with explosion protection
F
With signal cable interface adapter and explosion protection (*1)
3
With ISA Standard G3 and temperature (-20 to 70 ºC)
Option Codes
/A4S00
With pressure clamp terminal block for analog
[Model: STA4S-00]
/A4S10
With pressure clamp terminal block for analog (with surge absorber) [Model: STA4S-10]
/A4D00
With dual-redundant pressure clamp terminal block for analog (*2) [Model: STA4D-00]
/A4D10
With dual-redundant pressure clamp terminal block for analog (with surge absorber) (*2) [Part name: STA4D-10]
/PRP
With prevention pin of false insertion (*3)
/CCC01
With connector cover for MIL cable (for flat ribbon cable) [Model: SCCC01]
*1: When selecting SAV144-S63 or -SF3, you can not choose the option code of pressure clamp terminal block and MIL cable connector.
*2: When using this module in a dual-redundant configuration, order an additional module with the same specifications but without option codes.
*3: When SAV144-S63 or -SF3 is selected, you can choose the option code for prevention pin of false insertion.
A mechanism to prevent wrong type I/O module insertion is supported with signal cable. The signal cable used with this I/O
module must have option code /SAV144.
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.