Yokogawa EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25
overview
Yokogawa EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25
The high performance differential pressure transmitter model EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25 can be used to measure liquid, gas, or steam flow as well as liquid level, density and pressure. It outputs a 4 to 20 mA DC signal corre- sponding to the measured differential pressure. Model EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25 also features remote setup and monitoring through communications with the BRAIN™ terminal and CENTUM CS™ or μXL™ or HART® 275 host.
STANDARD SPECIFICATIONS
Yokogawa EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25
Refer to GS 01C22T02-00E for FOUNDATION Fieldbus communication type and GS 01C22T03-00E for
PROFIBUS PA communication type marked with “<.”
口 PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted parts material code ‘S’ and silicone oil.
Reference Accuracy of Calibrated Span
(including the effects of zero-based linearity, hyster- esis, and repeatability)
2:0.065% of Span
Failure Alarm
Output status at CPU failure and hardware error;
Up-scale: 110%, 21.6 mA DC or more(standard) Down-scale: -5%, 3.2 mA DC or less
-2.5%, 3.6 mA DC or less (Optional code /F1)
Note: Applicable for Output signal code D and E
Damping Time Constant (1st order)
The sum of the amplifier and capsule damping time constant must be used for the overall time constant. Amp damping time constant is adjustable from 0.2 to
64 seconds.
MODEL AND SUFFIX CODES
Yokogawa EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25
Model
|
Suffix Codes
|
Description
|
EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25
|
. . . . . . . . . . . . . . . . . . . . . . . . .
|
Differential pressure transmitter
|
Output Signal
|
-D . . . . . . . . . . . . . . . . . . . . . . .
-E . . . . . . . . . . . . . . . . . . . . . . .
-F . . . . . . . . . . . . . . . . . . . . . . .
-G . . . . . . . . . . . . . . . . . . . . . . .
|
4 to 20 mA DC with digital communication (BRAIN protocol)
4 to 20 mA DC with digital communication (HART protocol, refer to GS 01C22T01-00E) Digital communication (FOUNDATION Fieldbus protocol, refer to GS 01C22T02-00E) Digital communication (PROFIBUS PA protocol, refer to GS 01C22T03-00E)
|
Measurement span(capsule)
|
M . . . . . . . . . . . . . . . . . . . . . .
H . . . . . . . . . . . . . . . . . . . . . .
|
1 to 100 kPa { 100 to 10000 mmH2O} { 4 to 400 inH2O} { 10 to 1000 mbar}
5 to 500 kPa { 0.05 to 5 kgf/cm2} { 20 to 2000 inH2O} { 50 to 5000 mbar}
|
Wetted parts material *7
|
S# . . . . . . . . . . . . . . . . . . . .
|
[Body] [Capsule] [Vent plug] SUSF316 *1 SUS316L *2 SUS316 *8
|
Process connection
|
0 . . . . . . . . . . . . . . . . . . .
1 . . . . . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . . . . . .
3 . . . . . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . . . . . .
5 . . . . . . . . . . . . . . . . . . .
|
without process connector (Rc 1/4 female on the cover flanges)
with Rc 1/4 female process connector with Rc 1/2 female process connector
with 1/4 NPT female process connector *5
with 1/2 NPT female process connector *5
without process connector (1/4 NPT female on the cover flanges)
|
Bolts and nuts material
|
A . . . . . . . . . . . . . . . . . B . . . . . . . . . . . . . . . . . C . . . . . . . . . . . . . . . . .
|
[Maximum working pressure] SCM435 32 MPa {320 kgf/cm2} SUS630 32 MPa {320 kgf/cm2} SUH660 32 MPa {320 kgf/cm2}
|
Installation
|
-2 . . . . . . . . . . . . . . . .
-3 . . . . . . . . . . . . . . . .
-6 . . . . . . . . . . . . . . . .
-7 . . . . . . . . . . . . . . . .
-8 . . . . . . . . . . . . . . . .
-9 . . . . . . . . . . . . . . . .
|
Vertical impulse piping type, right side high pressure, process connector upside*3
Vertical impulse piping type, right side high pressure, process connector downside*3
Vertical impulse piping type, left side high pressure, process connector upside*3
Vertical impulse piping type, left side high pressure, process connector downside*3
Horizontal impulse piping type, right side high pressure*4
Horizontal impulse piping type, left side high pressure*4
|
Electrical connection
|
0 . . . . . . . . . . . . . . .
2 . . . . . . . . . . . . . . .
3 . . . . . . . . . . . . . . .
4 . . . . . . . . . . . . . . .
5 . . . . . . . . . . . . . . .
7 · · · · · · · · · · · · · · ·
8 · · · · · · · · · · · · · · ·
9 · · · · · · · · · · · · · · · A · · · · · · · · · · · · · · · C · · · · · · · · · · · · · · · D · · · · · · · · · · · · · · ·
|
G1/2 female, one electrical connection
1/2 NPT female, two electrical connections without blind plug Pg 13.5 female, two electrical connections without blind plug M20 female, two electrical connections without blind plug G1/2 female, two electrical connections and a blind plug
1/2 NPT female, two electrical connections and a blind plug Pg 13.5 female, two electrical connections and a blind plug M20 female, two electrical connections and a blind plug
G1/2 female, two electrical connections and a SUS316 blind plug
1/2 NPT female, two electrical connections and a SUS316 blind plug
M20 female, two electrical connections and a SUS316 blind plug
|
Integral indicator
|
D . . . . . . . . . . . . . .
E . . . . . . . . . . . . . . N . . . . . . . . . . . . . .
|
Digital indicator
Digital indicator with the range setting switch*6
(None)
|
Mounting bracket
|
A . . . . . . . . . . . .
B . . . . . . . . . . . . J . . . . . . . . . . .
C . . . . . . . . . . . . D . . . . . . . . . . . . K . . . . . . . . . . .
N . . . . . . . . . . . .
|
SECC Carbon steel 2-inch pipe mounting (flat type) SUS304 2-inch pipe mounting (flat type) SUS316 2-inch pipe mounting (flat type) SECC Carbon steel 2-inch pipe mounting (L type) SUS304 2-inch pipe mounting (L type) SUS316 2-inch pipe mounting (L type) (None)
|
Optional codes
|
/口 Optional specification
|
|
|
|
|
|
|
|
|
|
|
|
The ‘’ marks indicate the most typical selection for each specification. Example: EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25-DMS5A-92NA/口
The ‘#’marks indicate the construction materials conform to NACE material recommendations per MR01-75. For the use of
SUS316 material, there may be certain limitations for pressure and temperature. Please refer to NACE standards for details.
*1: Indicates material of cover flange. Material of process connector is SCS14A(SUS316 equivalent).
*2: Diaphragm material is Hastelloy C-276 or ASTM N10276. Other capsule wetted parts materials are SUSF316L, SUS316L or ASTM grade 316L.
*3: If necessary, specify Mounting bracket code C, D or K.
*4: If necessary, specify Mounting bracket code A, B or J.
*5: Lower limit of ambient and process temperature is -15oC.
*6: Not applicable for Output signal code F and G.
*7: Users must consider the characteristics of selected wetted parts material and the influence of process fluids. The use of inappropriate materials can result in the leakage of corrosive process fluids and cause injury to personnel and/or damage to plant facilities. It is also possible that the diaphragm itself can be damaged and that material from the broken diaphragm and the fill fluid can contaminate the user's process fluids.
Be very careful with highly corrosive process fluids such as hydrochloric acid, sulfuric acid, hydrogen sulfide, sodium hypochlorite, and high-temperature steam (150°C [302°F] or above). Contact Yokogawa for detailed information of the wetted parts material.
*8: SUS316 or ASTM grade 316.
PHYSICAL SPECIFICATIONS
Yokogawa EJA130A-FHS5B-99DA/X1/D4/M01/T09/KS25
Wetted Parts Materials
Diaphragm
Hastelloy C-276
Cover flange
SUSF316
Process connector
SCS14A
Capsule Gasket
Teflon-coated SUS316L
Vent and Drain Plug
SUS316 or ASTM grade 316
Process Connector Gasket
Glass reinforced Teflon (Process connection code 1 and 2)
Fluorinated rubber (Process connection code 3 and
4)
Non-wetted Parts Materials
Bolting
SCM435, SUS630, or SUH660
Housing
Low copper cast-aluminum alloy with polyurethane paint (Munsell 0.6GY3.1/2.0)
Degrees of Protection
IP67, NEMA4X
Cover O-rings
Buna-N, fluoro-rubber (optional)
Name plate and tag
SUS304 or SUS316 (option)
Fill Fluid
Silicone, Fluorinated oil (option)
Weight
6.8 kg (15.0 lb) without mounting bracket and process connector
Connections
Refer to the model code to specify the process and electrical connection type
Process Connection of Cover Flange:
DIN 19213 with 7/16 inch x 20 unf female thread.