Product Information

Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC[Product print page]

Product Name: Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC
Product Type: EJA115-FHS400B-63EC
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC is a flowmeter comprised of a differential pressure transmitter with an integral orifice. Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC


 Detailed description

Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC

 

 STANDARD SPECIFICATIONS

Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC

Refer to GS 01C22T02-00E for FOUNDATION Fieldbus communication type and GS 01C22T03-00E for

PROFIBUS PA communication type marked with 0.

Measurement Ranges:  

Capsule

Differential

Pressure Span

Water Equivalent Flow l/min

Air Equivalent Flow Nl/min

L

1 to 10 kPa

{100 to 1000 mmH2O}

0.016 to 7.2

0.44 to 198

M

2 to 100 kPa

{200 to 10000 mmH2O}

0.022 to 23.0

0.63 to 635

H

20 to 210 kPa

{2000 to 21000 mmH2O}

0.07 to 33.0

2.0 to 910

 Output Signal 0”:

4 to 20 mA DC, 2-wire system with digital communication

Failure Alarm:

Output status at CPU failure and hardware error;

Up-scale: 110%, 21.6 mA DC or more(standard) Down-scale: -5%, 3.2 mA DC or less

-2.5%, 3.6 mA DC or less (Optional code /F1)

Note: Applicable for Output signal code D and E

Supply Voltage “0”:
10.5 to 42 V DC for general use and flameproof type
10.5 to 32 V DC for lightning protector (Optional code /A)
10.5 to 30 V DC for intrinsically safe, Type n, nonincendive, or non-sparking type
10.5 to 28 V DC for TIIS intrinsically safe type
Conditions of Communication Line “0”: Power supply voltage; 16.4 to 42 V DC
Load resistance; See Figure 1.
Note:  In case of an intrinsically safe transmitter, external load resistance includes safety barrier resistance.
Communication distance;
2 km, when CEV polyethylene-insulated PVC- sheathed control cables are used.
Note:  Communication distance varies depends on kind of cable.
Load capacitance; 0.22 µF or less. Load inductance; 3.3 mH or less.
Spacing from power line; 15 cm or more.
Input impedance of receiver connected receiving resistance;
10 kf! or more at 2.4 kHz
(See Optional Specifications for Intrinsically safe type)
Accuracy:
::15 % of span
Ambient Temperature Limits: -40 to 85 OC (-40 to 185 OF) (general-use type)
-30 to 80 OC (-22 to 176 OF) (with integral indicator)
(See ‘Optional Specifications’ for Explosion-protected types)
Process Temperature Limits: -40 to 120 OC (-40 to 248 OF) (general use type)
(See ‘Optional Specifications’ for Explosion-protected types)
Ambient Humidity Limits: 5 to 100 % R.H.(at 40 OC)
Working Pressure Limits: 2.7 kPa abs{20 mmHg abs} to maximum working pressure
(See ‘Model and Suffix Codes’).
For atmospheric pressure or below, see Figure 2.
Power Supply Effect “0”: 10.005 %/V (21.6 to 32 V DC, 350 f!)
Mounting: 2-inch pipe mounting.
Mounting Position Effect: 390 Pa {40 mmH2O}/90 O.
No effect for displacement parallel to diaphragm.
These errors can be corrected by the zero adjustment.
Degrees of Protection:
IP67, NEMA4X
Explosion-protected Construction:
See ‘Optional Specification.’

 

Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC

External Zero Adjustment 0”: Continuously Adjustable Resolution; 0.01 % of span

Zero Adjustment Limits: Zero can be fully elevated or suppressed as long as low and high range values are within the measurement range limits of the capsule.

Tag Plate: JIS SUS304 or SUS316

Weight: 5.6 kg (12.4 lb) without integral indicator and mounting bracket.

Add 1.4 kg (3.1 lb) for JIS SCS14A stainless steel amplifier housing.

EMC Conformity Standards 0”: EN61326-1 Class A, Table2 (For use in industrial locations) EN61326-2-3

European Pressure Equipment Directive 97/23/EC: Sound Engineering Practice

Safety Requirement Standards: EN61010-1

Altitude of installation site: Max. 2,000 m above sea level

• Installation category: I

• Pollution degree: 2

• Indoor/Outdoor use


Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC

Electrical Connection: See ‘Model and Suffix Codes.’
Process Connections: See ‘Model and Suffix Codes.’
Wetted Parts Material: Diaphragm, cover flange, process connector, vent plug, manifold and orifice; See ‘Model and Suffix Codes.’
Capsule gaskets; Teflon-coated JIS SUS316L.
Process connector gasket; PTFE (Teflon)
Flange Bolts and Nuts Material:
See ‘Model and Suffix Codes.’
Amplifier Housing: Cast aluminum alloy or JIS SCS14A stainless steel(optional)
Painting: Polyurethane resin backed finish
Deep sea moss green (Munsell 0.6GY3.1/2.0)
Integral Indicator: LCD digital indicator (optional)
Damping Time Constant: (Sum of time constants for amplifier assembly and capsule assembly)
Amplifier assembly time constant;
Can be set in 9 increments from 0.2 to 64 sec. Capsule assembly time constant;


Settings  When  Shipped

 Yokogawa Low Flow Transmitter EJA115-FHS400B-63EC

Tag Number

As specified in order *1

Output Mode

‘Linear’ unless otherwise specified in order

Display Mode

‘Square root’

Operation Mode

‘Normal’ unless otherwise specified in order

Damping Time

Constant *2

‘2 sec.’


Calibration Range

Lower Range Value

As specified in order

Calibration Range

Higher Range Value

As specified in order

 

Calibration Range

Units

Selected from mmH2O, mmAq, mmWG, mmHg, Pa, hPa, kPa, MPa, mbar, bar, gf/cm2, kgf/cm2, inH2O, inHg, ftH2O, or psi. (Only one unit can be specified)


*1:     Up to 16 alphanumeric characters (including - and · ) will be entered in the amplifier memory.

*2:     If using square root output, set damping time constant to 2 sec. or more.