Product Information

Yokogawa Manual Setter YS1360-240[Product print page]

Product Name: Yokogawa Manual Setter YS1360-240
Product Type: YS1360-240
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Manual Setter YS1360-240 include as standard an operation mode selector switch [cascade (C) and manual (M)], status input-based operation mode selector function. Yokogawa Manual Setter YS136


 Detailed description

Yokogawa Manual Setter YS1360-240

  

 

GENERAL

Yokogawa Manual Setter YS1360-240

The YS1360-240 is a manual setter that allows for manually output-ting operation signals to operation terminals. YS1360-240 include as standard an operation mode selector switch [cascade (C) and manual (M)], status input-based operation mode selector function, and opera- tion mode discrimination status output function.YS1360-240 offer high reliability thanks to Yokogawa’s proprietary technology, user friendliness, and expandability. The basic type conforming to the DIN short case size contributes to space saving for mounting, and complies with standards (CE, FM*, and CSA*). For easy replacement of earlier models requiring the same panel cutout dimensions and depth as those of earlier models are also offered. *: To be approved.

 

FEATURES

Yokogawa Manual Setter YS1360-240

  Display functions

(1) Display specification

The screen is divided into Operation Display, Tuning Dis- play, and Engineering Display groups, and functions can be set on the setting display for each function.


 

Hardware Specification

Yokogawa Manual Setter YS1360-240

Input and output signal specification

 Analog input sigal

Specification

1 to 5 VDC

2 points, PV input and cascade input

Input resistance

1 M or more

Direct input (*1) (option)

One of the above 2 points (PV input)

possible

*1:Any one of mV,thermocouple, resisitance temperature detector potentiometer,2-wire transmitter,input isolator,or frequency input.

 

Model and Suffix Code

Yokogawa Manual Setter YS1360-240 

Model

Suffix Code

Optional Code

Remark

YS1350

Manual setter for SV Setting

YS1360-240

Manual setter for MV Setting

Use

-1

YS1350: Always -1

YS1360-240: With hard manual unit

-2

YS1360 only: Without hard manual unit

Type

0

Basic type

2

YS100 compatible type (with YS100 case)

3

YS80 internal unit compatible type, EBS, I, EK, HOMAC compatible type (*1)

4

YS80 compatible type (YS 80 compatible size, YS100 terminal type)

5

100 Line compatible type (YS100 terminal type) (*2)

Power supply

0

100 VAC and 24 VDC common power supply

1

220 VAC power supply

Direct input (*3)

/A01

mV input

/A02

Thermocouple input

/A03

Resistance temperature detector input

/A04

Potentiometer input

/A05

Isolator

/A06

2-wire transmitter input (insulation type)

/A07

2-wire transmitter input (non-insulation type)

/A08

Frequency input

/DF

Direct input with Fahrenheit temperature range function (*9)

Communication

/A31

RS-485 communication (PC link, Modbus, YS protocol) (*4)

/A32

DCS-LCS communication (*5)

/A34

Ethernet communication (Modbus/TCP) (*6)

Certification

/FM

FM nonincendive approved (FM Class I, Division 2) (*7) (To be approved)

/CSA

CSA safety and nonincendive approved (Class I, Division 2) (*8) (To be approved)

*1:  Can be connected with the YS80 housing (Model: SHUP-000). (The EK and HOMAC compatible housing SHUP-420 and EBS/I Series compatible hous-

ing SHUP-100 are available separately.)

*2:  The 100 Line compatible housing (Model: YS006) is available separately.

*3:  The direct input option can be added only for optional codes –x2x, -x4x, and -x5x. Multiple selections are not possible.

*4:  A combination with suffix code “-x3x is not possible. Optional codes /A31 and /A32 cannot be simultaneously specified.

Please specify the communication options /A31 (RS-485 communication) to directly communicate with the CENTUM CS3000/VP.

*5:  Optional codes /A31 and /A32 cannot be simultaneously specified. Please specify the communication options /A32 (DCS-LCS communication) to com-

municate with the CENTUM CS3000/VP through the SCIU.

*6:  Communication option /A34 can be specified only for suffix code –x0x.

*7:  Can be added only for suffix code –x0x.

*8:  Can be added only for suffix code –x0x and –x2x.

*9   This option can be combined only with option code /A02 or /A03.If option code /DF is specified, Fahrenheit temperature range can be available for direct input range in addition to Centigrade temperature range. In case of specifying Fahrenheit temperature range for direct input, option code /DF is required. When the direct input temperature range may be changed to Fahrenheit temperature range after shipment, also specify option code /DF.