Product Information

Yokogawa Indicator YS1310[Product print page]

Product Name: Yokogawa Indicator YS1310
Product Type: YS1310
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Indicator YS1310 is an input indicator that has alarms with two inputs. Yokogawa Indicator YS1310 offers high reliability thanks to Yokogawa’s proprietary technology, user friendliness.


 Detailed description

Yokogawa Indicator YS1310


GENERAL

Yokogawa Indicator YS1310

The YS1310 Indicator with Alarms is an input indicator that has alarms with two inputs. Two loops can be displayed simultaneously. A high limit alarm, low limit alarm, high-high limit alarm, and low-low limit alarm can be generated for each of the two inputs, and the AND connection or OR connection of arbitrary alarms can be output from a total of 6 contacts.

The YS1310 offers high reliability thanks to Yokogawa’s proprietary technology, user friendliness, and expandabil- ity. The basic type conforming to the DIN short case size contributes to space saving for mounting, and complies with standards (CE, FM* and CSA*). For easy replace- ment of earlier models requiring the same panel cutout dimensions and depth as those of earlier models are also offered. *: To be approved.


 FEATURES

Yokogawa Indicator YS1310

▪ A full-dot, FTF LCD Clear visibility of the display screen is ensured even in direct sunlight in the early morning and late afternoon.
The user can freely access a desired operation screen from meter, trend, bar graph, alarm, and event displays.
All parameters can be set via the front panel display.
▪ The parameters can all be set by operation on the front  panel (no need to draw out the internal unit).
▪ Parameters can also be set using YSS1000 Setting  Software available separately.
▪ Can be driven by either an AC (100 V) or DC (24 V)  power supply. (Must be specified upon ordering if using  a 220–240 V DC power supply.)
▪ Dust- and splash-proof IP54 faceplate (for basic type only)
▪ Depth 250 mm (only for the basic type)
▪ No battery or capacitor is used for memory backup. No maintenance is required because batteries and backup capacitors are not used.
▪ CE mark (for basic types and YS100-compatible type only)
▪ FM non-incentive explosion protection (option, for basic types only) (Under an application) (To be approved)
▪ CSA non-incentive explosion protection (option, for basic type, compatible type for YS100 (with YS100 case)) (To be approved)

▪ Communication (option)
  Ethernet (Modbus/TCP) (for basic types only)
  RS485 (PC Link, Modbus, YS protocol, unavailable for YS80 internal unit-compatible type)
▪ Compatibility with the YS100 series
Setting and control operations can be done with the same feel. In the case of the basic type, terminal-to-terminal pitches differ but the signal-to-terminal arrangement is almost the same. The following functions are included to ensure compatibility with the SIHK.
▪ Meter Display was added to the Operation Display.
▪ Housing for replacement purposes (SHUP-000 sepa- rately available)


Model and Suffix Code

Yokogawa Indicator YS1310

Model

Suffix Code

Optional Code

Remark

YS1310

 

Indicator with alarm

Use

-1

Always -1

 

 

Type

0

Basic type

2

YS100 compatible type (with YS100 case)

3

YS80 internal unit compatible type, EBS, I, EK, HOMAC compatible type (*1)

4

YS80 compatible type (YS 80 compatible size, YS100 terminal type)

5

100 line compatible type (YS100 terminal type) (*2)

 

Power supply

0

100 VAC and 24 VDC power supply

1

220 VAC power supply

 

 

 

 

 

Direct input (*3)

/A01

mV input

/A02

Thermocouple input

/A03

Resistance temperature detector input

/A04

Potentiometer input

/A05

Isolator

/A06

2-wire transmitter input (insulation type)

/A07

2-wire transmitter input (non-insulation type)

/A08

Frequency input

/DF

Direct input with Fahrenheit temperature range function (*7)

 

Communication

/A31

RS-485 communication (PC link, Modbus, YS protocol) (*4)

/A34

Ethernet communication (Modbus/TCP) (*5)

 

Certification

/FM

FM nonincendive approved (FM Class I, Division 2) (*6) (To be approved)

/CSA

CSA safety and nonincendive approved (Class I, Division 2) (*8) (To be approved)

*1:  Can be connected with the YS80 housing (Model: SHUP-000). (The EK and HOMAC compatible housing SHUP-420 and EBS/I series compatible housing SHUP-100 are available separately.)

*2:  The 100 line compatible housing (Model: YS006) is available separately.

*3:  The direct input option can be added only for suffix codes –12x, -14x, and -15x. Multiple selections are not possible.

*4:  Can not be added for suffix code –13x.

*5:  /A34 can be specified only for suffix code –10x.

*6:  Can be added only for suffix code –10x.

*7   This option can be combined only with option code /A02 or /A03.If option code /DF is specified, Fahrenheit temperature range can be available for direct

input range in addition to Centigrade temperature range. In case of specifying Fahrenheit temperature range for direct input, option code /DF is required.

When the direct input temperature range may be changed to Fahrenheit temperature range after shipment, also specify option code /DF.

*8   Can be added only for suffix code –10x and –12x.


 Display and Setting Functions

Yokogawa Indicator YS1310

● Display functions

    Display specification

   YS1700 displays are composed of the following three groups and the individual functions can be set up via displays for the respective settings:

    

 

 

Operation displays

LOOP displays TREND displays ALARM displays DUAL displays METER displays

FAIL display (when a failure occurs)

 

Tuning displays

Setting display

Input/output data display

 

 

Engineering

Function settings

Input specification settings Password setting Operation display settings LCD settings Communication settings