Yokogawa Program Controller UP55A-100-11-00
Overview
Features
• A 14-segment, active (PV display color changing function) color LCD display is employed. Two five-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read manner. The guide display shows parameter names. • Easy to operate Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys) are employed to facilitate making settings. • 65 mm depth The small depth enables the mounting in a thin and small instrumented panel. • Ladder sequence function is included as standard. This function allows for creating a simple sequence control. Dedicated LL50A Parameter Setting Software (sold separately) allows for performing programming using a ladder language. • Various built-in open network functions such as Ethernet are available. Easy connection with various vendors’ PLCs is possible. • Quick setting function Setting only the minimum necessary parameters for operation is possible. (For single-loop control only) • Equipped with a multitude of functions Universal I/O and eight control modes (cascade control, etc) are included as standard. PID control, heating/cooling control, feed forward control, etc. are available.
Construction, Installation, and Wiring
• Material: Polycarbonate (Flame retardancy: UL94V-0) • Case color: White (Light gray) or Black (Light Charcoal gray) • Weight: 0.5 kg or less • External dimensions (mm): 96 (W) × 96 (H) × 65 (depth from the panel face) (Depth except the projection on the rear panel) • Installation: Direct panel mounting; mounting bracket, one each for upper and lower mounting • Panel cutout dimensions (mm): 92+0.8/0 (W) × 92+0.8/0 (H) • Mounting attitude: Up to 30 degrees above the horizontal. No down • Dust-proof and drip-proof: IP66 (for front panel) (Not available for side-by-side close mounting.) ward titling allowed. • Wiring: M3 screw terminal with square washer (for signal wiring and power wiring)
Model and Suffix Code
Model Suffix code Optional suffix code Description UP55A-100-11-00 Program Controller (provided with retransmission output or 15 V DC loop power supply, 8 DIs, and 8 DOs) (Power supply: 100-240 V AC) 30 program patterns / 300 program segments (Max. 99 segments per pattern) Type 1: Basic control -0 Standard type -1 Position proportional type -2 Heating/cooling type Type 2: Functions (*1) 0 None 1 Remote (1 additional aux. analog) input, 1 additional DI 2 RS-485 communication (Max.19.2 kpbs, 2-wire/4-wire) 3 10 additional DOs 4 3 additional aux. analog inputs, 2 DIs and 5 DOs to be deleted Type 3: Open networks 0 None 1 RS-485 communication (Max.38.4 kbps, 2-wire/4-wire) 2 Ethernet communication (with serial gateway function) 3 CC-Link communication (with Modbus master function) 4 PROFIBUS-DP communication (with Modbus master function) 5 DeviceNet communication (with Modbus master function) Display language (*2) -1 English -2 German -3 French -4 Spanish Case color 0 White (Light gray) 1 Black (Light charcoal gray) Fixed code -00 Always “-00” Optional suffix codes /DR Additional direct input (TC and 3-wire/4-wire RTD) and current input to Remote (1 additional aux. analog) input, 1 DI to be deleted (*3) /HA Heater break alarm (*4) /DC Power supply 24 V AC/DC /CT Coating (*5)
Model
Suffix code
Optional suffix code
Description
UP55A-100-11-00
Program Controller (provided with retransmission output or 15 V DC loop power supply, 8 DIs, and 8 DOs) (Power supply: 100-240 V AC)
30 program patterns / 300 program segments (Max. 99 segments per pattern)
Type 1:
Basic control
-0
Standard type
-1
Position proportional type
-2
Heating/cooling type
Type 2: Functions (*1)
0
None
1
Remote (1 additional aux. analog) input, 1 additional DI
2
RS-485 communication (Max.19.2 kpbs, 2-wire/4-wire)
3
10 additional DOs
4
3 additional aux. analog inputs, 2 DIs and 5 DOs to be deleted
Type 3:
Open networks
RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)
Ethernet communication (with serial gateway function)
CC-Link communication (with Modbus master function)
PROFIBUS-DP communication (with Modbus master function)
5
DeviceNet communication (with Modbus master function)
Display language (*2)
English
German
-3
French
-4
Spanish
Case color
White (Light gray)
Black (Light charcoal gray)
Fixed code
-00
Always “-00”
Optional suffix codes
/DR
Additional direct input (TC and 3-wire/4-wire RTD) and current input to Remote (1 additional aux. analog) input, 1 DI to be deleted (*3)
/HA
Heater break alarm (*4)
/DC
Power supply 24 V AC/DC
/CT
Coating (*5)
*1: When “3” is specified for the Type 2 code, only “0” can be specified for the Type 3 code. *2: English, German, French, and Spanish can be displayed as the guide display. *3: When any of “1” or “4” is specified for the Type 2 code, the /DR option can be specified. *4: When “-0” is specified for the Type 1 code, the /HA option can be specified. *5: When the /CT option is specified, the UP55A-100-11-00 does not conform to the safety standards (UL and CSA) and CE marking.
Contact Number: +86 13724889019 Email: tekrachel2024@163.com Web: www.tek-international.com WeChat: tekrachel tekrachel@163.com
Add.: Room 2401 Building D Greenland Central Plaza, Science City, Huangpu District, Guangzhou 510663, Guangdong Province, China.