Brief

Yokogawa Manual Setter UD320-00 can be used as a remote setter for digital indicating controllers like GREEN series controllers. Yokogawa Manual Setter UD320-00


 Detailed description

Yokogawa Manual Setter UD320-00


General

Yokogawa Manual Setter UD320-00

The UD300 series manual setters have PV display, and transmit 4 to 20mA DC by manual operation.  It can be
used as a remote setter for digital indicating controllers like
GREEN series controllers.
The SP (target setpoint) will be output in 3 seconds after the change.
The TC, RTD or Voltage input is possible as PV input. When the PV display is not necessary, it can be disap- peared.
The two alarm outputs and a PV retransmission output are provided as standard.
The front panel has a splash-proof and dust-proof design
(IP65), which enables the use in the dusty environment.



Model and Suffix Codes

Yokogawa Manual Setter UD320-00

Model

Suffix code

Description

UD320-00

UD320

UD350

 

UD320-00 Manual Setter   4 to 20 mADC output (48X48X100 mm) UD320 Manual Setter   4 to 20 mADC output (48X96X100 mm) UD350 Manual Setter   4 to 20 mADC output (96X96X100 mm)

Fixed code

–0

Always 0

Fixed code

0

Always 0

Option

/V24

Power Supply 24V DC / 24V AC

* 2 Alarm outputs and PV retransmission output in 4 to 20 mA built in as standard. 

   Check the package contents against the list below

• Manual Setter ..................................... 1
• Mounting bracket ................................ 1 for UD320-00
2 for UD320, UD350
• User's manual ..................................... 1


Construction, Mounting, and Wiring

Yokogawa Manual Setter UD320-00

 • Construction: Dust-proof and splash-proof front panel (compliant with IP65 [Model UD320-00] and
IP55 [Models UD320 and 350]). Splash-proof construction is not available for side-by-side close mounting.
• Casing: ABS resin and polycarbonate
• Case color: Black
• Weight: UD320-00 - approx. 200g
UD320 - approx. 300g
UD350 - approx. 400g
• Mounting: Flush panel mounting
• Wiring: Screw terminals



Measured Value (PV) Input

Yokogawa Manual Setter UD320-00


• Input: 1 point
• Input type: Universal; can be selected by software
• Input accuracy (at 23 ±2°C ambient temperature)
• Thermocouple: ±2°C  ±1digit
However,
• ±4°C for thermocouple input –200 to –100°C
• ±3°C for thermocouple input –100 to 0°C
• ±5°C for types R and S (±9°C for 0 to 500°C)
• ±9°C  for type  B (accuracy is not guaranteed for 0 to 400°C)
• RTD: ±1°C  ±1digit
•Voltage(mV, V) : ±0.3%  ±1digit
• Sampling period for measured value input: 500ms
• Burn-out detection: Functions for thermocouple or RTD input
(burn-out upscale only; cannot be switched off)
• Input resistance: 1MΩ or greater for thermocouple
or DC mV input. Approx. 1MΩ for DC V input
• Maximum allowable signal source resistance :
250Ω for thermocouple or DC mV input
2kΩ for DC V input
• Maximum allowable wiring resistance for RTD input:
10Ω/wire (The resistance values of three wires must be the same.)
• Allowable input voltage: ±10V DC for thermocouple or DC mV input
±20V DC for DC V input
• Noise rejection ratio: Normal mode noise: Min. 40dB
(50/60Hz)               Common mode noise: Min. 120dB
(Min. 90dB for DC V input)
• Error of reference junction compensation:±1.5°C (at 15-35°C)
±2.0°C (at 0-50°C)
The reference junction compensation cannot be switched off.
• Applicable standards:
Thermocouple and resistance temperature detector(RTD)
JIS/IEC/DIN (ITS90)


Safety and EMC Standards

Yokogawa Manual Setter UD320-00




• Safety: Compliant with IEC/EN61010-1 (CE), IEC/EN61010-2-030 (CE), approved by CAN/CSA C22.2 No.61010-1 (CSA), approved by UL61010-1.

Installation category: II, Pollution degree: 2
Measurement category: I (CAT I) (UL, CSA)
O (Other) (CE)
Rated measurement input voltage: Max. 10 V DC
Rated transient overvoltage: 1500 V (*)
* This is a reference safety standard value for measurement category I of
IEC/EN/CSA/UL61010-1. This value is not necessarily a guarantee of instrument performance.
• EMC standards: Complies with EN61326
The UD300 series manual setters conform to the standards specified under the following conditions.
All wires except those for the power supply and relay contact output terminals are shielded.
The controller does not fluctuate more than 20% even when noise is applied.
• KC marking:
Electromagnetic wave interference prevention standard, electromagnetic wave protection standard compliance.