Product Information

Yokogawa Limit Controller UT150-RN/AL[Product print page]

Product Name: Yokogawa Limit Controller UT150-RN/AL
Product Type: UT150-RN/AL
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Limit Controller UT150-RN/AL is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user. Yokogawa Limit Controller UT150-RN/AL


 Detailed description

Yokogawa Limit Controller UT150-RN/AL


General

Yokogawa Limit Controller UT150-RN/AL

The UT150-RN/AL is an FM approved limit controller that can be configured either as a high limit or as a low limit controller by a user.
The UT150-RN/AL features universal input, two alarm outputs, retransmission output, a timer to count the total time the setpoint is exceeded, and a register to retain the maximum temperature reached.
The RS485 communication interface is available optionally.



 Model and Suffix Codes

Yokogawa Limit Controller UT150-RN/AL

Model           Suffix Codes

Descriptions

UT150-RN/AL

 

Limit Controller (1/16 DIN size)

Control output

–R

Relay output

Fixed code

N

Always N

Option

/AL

/EX

/RET

/RS

Alarm outputs (2 points) Digital input (1 point)

PV retransmission output in 4 to 20 mA Communication function

 


Hardware Specifications

Yokogawa Limit Controller UT150-RN/AL

Measured Value (PV) Input

• Input: 1 point

• Input type: Universal; can be selected by software
• Input accuracy (at 23 2C ambient temperature)
• Thermocouple: 2C1digit
However,
• 4C for thermocouple input –200 to –100C
• 3C for thermocouple input –100 to 0C
• 5C for type R and S (9C for 0 to 500C)
• 9C for type B (accuracy is not guaranteed for 0 to 400C)
• RTD: 1C1digit
• Voltage (mV, V): 0.3%1digit
• Sampling period for measured value input: 500ms
• Burnout detection: Functions for thermocouple
or RTD input (burnout upscale only; cannot be
switched off)
• Input resistance: 1M or greater for thermocouple or
DC mV input. Approx. 1M for DC V input
• Maximum allowable signal source resistance :
250 for thermocouple or DC mV input
2k for DC V input
• Maximum allowable wiring resistance for RTD input:
10/wire (The resistance values of three wires
must be the same.)
• Allowable input voltage:
10V DC for thermocouple or DC mV input
20V DC for DC V input
• Noise rejection ratio:
Normal mode noise: Min. 40dB (50/60Hz)
Common mode noise: Min. 120dB (Min. 90dB
for DC V input)
• Error of reference junction compensation:
1.5C (at 15-35C)
2.0C (at 0-50C)
The reference junction compensation cannot be switched off.
• Applicable standards:
Thermocouple and resistance temperature
detector JIS/IEC/DIN (ITS90)
•Response time:
2 second or less, 63% (10 - 90%)
(The time required for transmission output to reach 63% of the maximum excursion when PV abruptly changes from 10% to 90%)



Control output

Yokogawa Limit Controller UT150-RN/AL

• Output: 1 point
• Output type:
Relay contact output
Contact capacity: 3A at 240V AC or 3A at 30V DC (with resistance load)
Note: The control output relay cannot be replaced by users.