Product Information

Yokogawa Limit Controller UT35A-L02-10-00/DC[Product print page]

Product Name: Yokogawa Limit Controller UT35A-L02-10-00/DC
Product Type: UT35A-L02-10-00/DC
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa Limit Controller UT35A-L02-10-00/DC is a Limit Control Type Digital Indicating Controller. Yokogawa Limit Controller UT35A-L02-10-00/DC complies with FM approval.


 Detailed description

Yokogawa Limit Controller UT35A-L02-10-00/DC


Overview

Yokogawa Limit Controller UT35A-L02-10-00/DC

The UT35A-L02-10-00/DC features universal input, three alarm outputs, retransmission output, a timer to count the total time the setpoint is exceeded, and a register

to retain the maximum temperature reached.  The UT35A-L02-10-00/DC controller employs an easy-to-read, 14-seg- ment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities.  The short depth of the control- ler helps save instrument panel space.  The UT35A-L02-10-00/DC also support RS-485 and Ethernet communication.
 

 Features

Yokogawa Limit Controller UT35A-L02-10-00/DC

• A 14-segment, active (PV display color changing function) color LCD display is employed.
Two five-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read manner. The guide display shows parameter names.
• Easy to operate
Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys) are employed to facilitate making settings.
• 65 mm depth
The small depth enables the mounting in a thin and small instrumented panel.
• Quick setting function
Setting only the minimum necessary parameters for operation is possible.


Construction, Mounting, and Wiring

Yokogawa Limit Controller UT35A-L02-10-00/DC

• Degree of protection provided by Enclosure: IP66 (for front panel) (Not available for side-by-side close mounting.)

• Material: Polycarbonate resin (Flame retardancy: UL94 V-0)
• Case color: Light gray or Light charcoal gray
• Weight: 0.5 kg or less
• External dimensions (mm): 96 (width) x 96 (height) x 65 (depth from the panel surface)
• Mounting: Direct panel mounting; mounting bracket, one each for upper and lower mounting
• Panel cutout dimensions (mm): 92+0.8/0 (width) x 92+0.8/0 (height)
• Mounting position: Up to 30 degrees above the horizontal. No downward titling allowed.
• Wiring: M3 screw terminal with square washer (signal wiring and power)


Contact Input Specifications

Yokogawa Limit Controller UT35A-L02-10-00/DC

• Number of points: 2 points
• Input type: no-voltage contact input or transistor con- tact input
• Input contact capacity: 12 V DC, 10 mA or more Be sure to use a contact with a minimum ON current of 1 mA or more
• ON/OFF detection
No-voltage contact input:
Contact resistance 1 kΩ or less in ON state
Contact resistance 50 kΩ or more in OFF state
Transistor contact input:
2 V or less in ON state
Leak current 100 μ A or less in OFF state
• Status detection minimum hold time: 250 ms
• Application: Confirmation operation, etc.


Model and Suffix Code

Yokogawa Limit Controller UT35A-L02-10-00/DC 

 

Model

 

Suffix code

Optional suffix code

 

Description

UT35A

 

 

Digital Indicating Controller (provided with retransmission output, 2 DIs, and 3 DOs)

(Power supply: 100-240 V AC)

Type 1:

Basic control

-L

 

 

 

 

 

 

Limit control type

Type 2:

Functions

0

 

 

 

 

 

Always "0"

Type 3:

Open networks

0

 

 

 

 

None

1

 

 

 

 

RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)

2

 

 

 

 

Ethernet communication (with serial gateway function)

Display language

-1

 

 

 

English

Case color

0

 

 

White (Light gray)

1

 

 

Black (Light charcoal gray)

Fixed code

-00

 

Always "-00"

Optional suffix codes

/DC

Power supply 24 V AC/DC