Yokogawa Limit Controller UT35A-L00-11-00/DC
Overview
Yokogawa Limit Controller UT35A-L00-11-00/DC
The UT35A-L00-11-00/DC features universal input, three alarm outputs, retransmission output, a timer to count the total time the setpoint is exceeded, and a register
to retain the maximum temperature reached. The UT35A-L00-11-00/DC controller employs an easy-to-read, 14-seg- ment large color LCD display, along with navigation keys, thus greatly increasing the monitoring and operating capabilities. The short depth of the control- ler helps save instrument panel space. The UT35A-L00-11-00/DC also support RS-485 and Ethernet communication.
Features
Yokogawa Limit Controller UT35A-L00-11-00/DC
• A 14-segment, active (PV display color changing function) color LCD display is employed.
Two five-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read manner. The guide display shows parameter names.
• Easy to operate
Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys) are employed to facilitate making settings.
• 65 mm depth
The small depth enables the mounting in a thin and small instrumented panel.
• Quick setting function
Setting only the minimum necessary parameters for operation is possible.
Construction, Mounting, and Wiring
Yokogawa Limit Controller UT35A-L00-11-00/DC
• Degree of protection provided by Enclosure: IP66 (for front panel) (Not available for side-by-side close mounting.)
• Material: Polycarbonate resin (Flame retardancy: UL94 V-0)
• Case color: Light gray or Light charcoal gray
• Weight: 0.5 kg or less
• External dimensions (mm): 96 (width) x 96 (height) x 65 (depth from the panel surface)
• Mounting: Direct panel mounting; mounting bracket, one each for upper and lower mounting
• Panel cutout dimensions (mm): 92+0.8/0 (width) x 92+0.8/0 (height)
• Mounting position: Up to 30 degrees above the horizontal. No downward titling allowed.
• Wiring: M3 screw terminal with square washer (signal wiring and power)
Contact Input Specifications
Yokogawa Limit Controller UT35A-L00-11-00/DC
• Number of points: 2 points
• Input type: no-voltage contact input or transistor con- tact input
• Input contact capacity: 12 V DC, 10 mA or more Be sure to use a contact with a minimum ON current of 1 mA or more
• ON/OFF detection
No-voltage contact input:
Contact resistance 1 kΩ or less in ON state
Contact resistance 50 kΩ or more in OFF state
Transistor contact input:
2 V or less in ON state
Leak current 100 μ A or less in OFF state
• Status detection minimum hold time: 250 ms
• Application: Confirmation operation, etc.
Model and Suffix Code
Yokogawa Limit Controller UT35A-L00-11-00/DC
Model
|
Suffix code
|
Optional suffix code
|
Description
|
UT35A
|
|
|
Digital Indicating Controller (provided with retransmission output, 2 DIs, and 3 DOs)
(Power supply: 100-240 V AC)
|
Type 1:
Basic control
|
-L
|
|
|
|
|
|
|
Limit control type
|
Type 2:
Functions
|
0
|
|
|
|
|
|
Always "0"
|
Type 3:
Open networks
|
0
|
|
|
|
|
None
|
1
|
|
|
|
|
RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)
|
2
|
|
|
|
|
Ethernet communication (with serial gateway function)
|
Display language
|
-1
|
|
|
|
English
|
Case color
|
0
|
|
|
White (Light gray)
|
1
|
|
|
Black (Light charcoal gray)
|
Fixed code
|
-00
|
|
Always "-00"
|
Optional suffix codes
|
/DC
|
Power supply 24 V AC/DC
|