Product Information

Yokogawa DCS Module AAI143-S00, AAI143-S50[Product print page]

Product Name: Yokogawa DCS Module AAI143-S00, AAI143-S50
Product Type: AAI143-S00 AAI143-S50
Exhibitors: Yokogawa
Product Documentation: No Related Documents

Brief

Yokogawa DCS Module AAI143-S00, AAI143-S50, Yokogawa DCS Module AAI143-S00, AAI143-S50. Yokogawa CENTUM VP. Yokogawa DCS Stock. Yokogawa DCS Spare Par. Please contact us: tekrachel @ 163.com


 Detailed description

Manufacturer: Yokogawa Electric Corporation

Yokogawa DCS Module AAI143-S00, AAI143-S50 

Yokogawa CENTUM VP

STANDARD SPECIFICATIONS

Current/Voltage Input Modules (Non-Isolated)

Yokogawa DCS Module AAI143-S00, AAI143-S50

These modules mainly receive 4 to 20 mA DC or 1 to 5 V DC standardized signal from 2-wire/4-wire transmitters.

They can be used in dual redundant configuration.

*1: This Yokogawa Analog Input Module AAI141 does not allow a Zener barrier to be connected. If the module Yokogawa DCS Module AAI143-S00, AAI143-S50 is to be used in intrinsically safe applications, use an isolation barrier.

*2: Viewed from the terminals, module input resistance is, depending on the current flowing:

250 Ω +(voltage drop (3 V maximum) in the input protection circuit)/(current value)

*3: This Yokogawa DCS Module AAI143-S00, AAI143-S50 voltage is developed between connecting terminals for this module’s 2-wire transmitter. When calculating if transmitter minimum operating voltage requirement will be satisfied, remember to allow for voltage drop in external wiring.

*4: R3.02 or later version supports HART function. When installing the module with HART function to a remote node, the firmware of EB401 must be Rev 2 or later.

For HART function specifications, refer to “HART Communication Package (for A□I□□□-H) (GS 33Q03L70-31E).”

MODELS AND SUFFIX CODES

Yokogawa DCS Module AAI143-S00, AAI143-S50

 

 

Description

Model

AAI141

Analog Input Module (4 to 20 mA, 16-channel, Non-Isolated)

Suffix Codes

-S

Standard type

-H

With digital communication (HART protocol)

5

With no explosion protection

E

With explosion protection

0

Basic type

3

With ISA Standard G3 option and temperature (-20 to 70 °C) option

Option Codes

/K4A00

With KS Cable Interface Adapter [Model: ATK4A-00]

/A4S00

With Pressure Clamp Terminal Block for Analog [Model: ATA4S-00]

/A4S10

With Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4S-10]

/A4D00

With Dual Pressure Clamp Terminal Block for Analog [Model: ATA4D-00]

/A4D10

With Dual Pressure Clamp Terminal Block for Analog (surge absorber) [Model: ATA4D-10]

/CCC01

With Connector Cover for MIL Cable [Model: ACCC01]