Yokogawa Temperature Controller UT35A
General
The Yokogawa Temperature Controller UT35A employ an easy-to-read, 14-segment large color LCD display, along with navigation keys, thus greatly increasing
the monitoring and operating capabilities. A ladder sequence function is included as standard. The short depth of the controller helps save instrument panel space. The Yokogawa Temperature Controller UT35A also support open networks such as Ethernet communication.
Features
• A 14-segment, active (PV display color changing function) color LCD display is employed.
Two five-digit, high-resolution displays are possible. Alphabet letters can be displayed in an easy-to-read manner. The guide display shows parameter names.
• Yokogawa Temperature Controller UT35A Easy to operate
Navigation keys (SET/ENTER and Up/Down/Left/ Right arrow keys) are employed to facilitate making settings.
• 65 mm depth
The small depth enables the mounting in a thin and small instrumented panel.
• Ladder sequence function is included as standard. This function allows for creating a simple sequence control. Dedicated LL50A Parameter Setting Software (sold separatly) allows for performing programming using a ladder language.
• Various built-in open network functions such as Eth- ernet are available.
Easy connection with various vendors’ PLCs is possible.
• Yokogawa Temperature Controller UT35A Quick setting function
Setting only the minimum necessary parameters for operation is possible.
• Yokogawa Temperature Controller UT35A Equipped with a multitude of functions
Universal I/O are included as standard. PID control, heating/cooling control, etc. are available.
Models and Suffix Codes
Yokogawa Temperature Controller UT35A
Model
|
Suffix code
|
Optional suffix code
|
Description
|
UT35A
|
|
|
Digital Indicating Controller (provided with retransmission output or 15 V DC loop power
supply, 2 DIs, and 3 DOs) (Power supply: 100-240 V AC)
|
Type 1:
Basic control
|
-0
|
|
|
|
|
|
|
Standard type
|
-1
|
|
|
|
|
|
|
Position proportional type
|
-2
|
|
|
|
|
|
|
Heating/cooling type
|
Type 2: Functions
|
0
|
|
|
|
|
|
None
|
1
|
|
|
|
|
|
2 additional DIs, 2 additional DOs
|
2
|
|
|
|
|
|
5 additional DIs, 5 additional DOs
|
Type 3:
Open networks
|
0
|
|
|
|
|
None
|
1
|
|
|
|
|
RS-485 communication (Max.38.4 kbps, 2-wire/4-wire)
|
2
|
|
|
|
|
Ethernet communication (with serial gateway function)
|
3
|
|
|
|
|
CC-Link communication (with Modbus master function)
|
4
|
|
|
|
|
PROFIBUS-DP communication (with Modbus master function)
|
5
|
|
|
|
|
DeviceNet communication (with Modbus master function)
|
Display language (*1)
|
-1
|
|
|
|
English
|
-2
|
|
|
|
German
|
-3
|
|
|
|
French
|
-4
|
|
|
|
Spanish
|
Case color
|
0
|
|
|
White (Light gray)
|
1
|
|
|
Black (Light charcoal gray)
|
Fixed code
|
-00
|
|
Always "-00"
|
Optional suffix codes
|
/LP
|
24 V DC loop power supply (*2)
|
/HA
|
Heater break alarm (*3)
|
/DC
|
Power supply 24 V AC/DC
|
/CT
|
Coating (*4)
|
*1: English,
German, French, and Spanish can be displayed as the guide display.
*2: The /LP option can be specified in the combination of Type 2 code (any of "0" or "1") and Type 3 code (any of "0" or "1".)
*3: The /HA option can be specified when the Type 1 code is "-0" or "-2."
*4: When the /CT option is specified, the UT35A does not conform to the safety standards (UL and CSA) and CE marking.